SERIES TT : STANDARD PADDLE WHEEL SENSOR

FEATURES/BENEFITS:

  • FLOW RANGES Image of Standard Paddle Wheel Sensor
    0.5 – 15 GPM (gal/min) 1.5 – 50 GPM
  • PRESSURE
    Working pressure up to 500 psi (up to 200 psi w/ optional clear cover)
  • ACCURACY
    ± 2% of full scale or better
  • REPEATABILITY
    ± 0.5% of full scale or better Reads in GPM and LPM scale
  • LINEAR TURN DOWN RATIO
    10:1
  • TEMPERATURE
    Fluid temperature of 20° to 225°F
  • FILTRATION
    150 microns
  • END CONNECTIONS
    NPT(F)

GENERAL DESCRIPTION:

Benefits:

CHOICE OF THREE PORT SIZES
Select from 1/2” , 3/4” or 1” NPT(F) porting to meet system requirements.

EASY MAINTENANCE AND CLEANING
Has only one moving component, the impeller. Cleaning and maintenance may be performed without removing the sensor from the piping.

SEVERAL OUTPUTS AVAILABLE
The standard interface is a 2-wire, 4-20mA current loop. Sensor signal may be transmitted on a low cost wire without degradation. Pulse and 0-5 VDC are also available.

HERMETICALLY ENCAPSULATED CIRCUITRY Withstands the harshest environments.

CONNECTS DIRECTLY TO YOUR FLOW MONITORING INSTRUMENTS
Can be connected directly to analog acquisition cards, chart recorders or other monitoring instruments, without external signal conditioning.

SIMPLY PLUMB AND APPLY POWER
Comes factory calibrated to your fl ow range specifi cations. VALUE PRICING Combined with low cost operation and maintenance, equals better bottom line savings for your operation.

 

series-tt-data-flow13

 

ELECTRICAL DATA

4-20 mA Version:
Power requirements: 12 – 35 VDC, loop powered
Load driving capacity 1150 Ohms maximum
Maximum transmitting distance Limited only by wire resistance & supply voltage
Response time 2 seconds to 90% (step change)
Resolution Infinite
Over-current limit Self limiting at 35 mA
Other protection Reverse polarity
0-5 VDC Version:
Power requirements 12 – 35 VDC
Maximum current 25 mA DC
Minimum load resistance 1000 Ohms
Maximum transmission distance 200 feet recommended
Response time > 5 seconds to 90% (step change)
Resolution Infinite
Pulse Output Version:
Power requirements 5 – 24 VDC
Maximum current 25 mA DC
Minimum load resistance 1000 Ohms
Maximum transmission distance 200 feet recommended
Response time < 100 mS
Protection Short circuit & reverse polarity
K-Factor 1/2″ port = 200 pulses/gallon
3/4′ & 1″ ports = 60 pulses/gallon
Relay Output Version:
Power requirement 12 – 35 VDC
Maximum transmission distance 200 feet recommended
Switch contact Form C, 5A max @ 120 or 240 VAC
Hysteresis 5% of set point maximum
Set point repeatability 1% of full scale

 

series-tt-data-flow12

Meter Dimensions

DIM 1/2″ NPTF 3/4″ – 1″ NPTF
A 1.94″ {49mm} 3.06″ {78mm}
B 1.13″ {29mm} 1.33″ {34mm}
C 2.00″ {51mm} 2.46″ {62mm}
D 2.60″ {66mm} 2.88″ {73mm}
E 3.70″ {94mm} 5.25″ {133mm}
F 2.63″ {67mm} 3.80″ {97mm}